Modular Conceptpower 120 UPS

Today’s data centers require continuous uptime. That target is why ABB’s Conceptpower DPA 120 is based on Decentralized Parallel Architecture (DPA). Only a truly redundant architecture like DPA allows online modules to be swapped out while the system is running. Each high-reliability, standardized module is self-contained and can be swapped at any time, so nothing has to be ever switched off – making routine maintenance safe and easy.

 

Conceptpower DPA 120 is designed to secure continuity of critical operations for small to mid-sized data centers, server rooms and other IT applications. It also protects industrial automation processes, healthcare facilities and many other vertical markets where operations are of a critical nature.

Modular Conceptpower 120 UPS

Today’s data centers require continuous uptime. That target is why ABB’s Conceptpower DPA 120 is based on Decentralized Parallel Architecture (DPA). Only a truly redundant architecture like DPA allows online modules to be swapped out while the system is running. Each high-reliability, standardized module is self-contained and can be swapped at any time, so nothing has to be ever switched off – making routine maintenance safe and easy.

 

Conceptpower DPA 120 is designed to secure continuity of critical operations for small to mid-sized data centers, server rooms and other IT applications. It also protects industrial automation processes, healthcare facilities and many other vertical markets where operations are of a critical nature.

Product Description

Designed for small to medium-sized data centers, Conceptpower 120 fulfills power requirements from 20 kW to 600 kW.

Request a Quote
Features

BASIC SYSTEM CONFIGURATION THE MODULE INCLUDES:

  • 20kW
  • True online double conversion UPS
  • Built-in modular isolation
  • Built-in backfeed protection
  • Individual module display
  • HMI interface with mimic diagram and LCD providing information in five languages

THE FRAME INCLUDES:

  • 120kW rated power in single frame
  • Bottom cable entry (standard)
  • Rectifier, bypass terminals (single or dual-input mains connection available) and UPS output terminals
  • Battery breakers and output switches for each module set
  • Graphical color touch screen system display
  • Communication interfaces: RS-232 and USB ports, I/O dry contacts (e.g. EPO, GEN On) and external bypass interlock

OPTIONS

  • Battery monitoring
  • Seismic bracing
  • Maintenance bypass cabinet
  • Control and monitoring (Modbus RS-485, Modbus TCP/IP, SNMP, Bacnet and others)
  • Line-and-match battery cabinets
Specifications

GENERAL DATA Conceptpower DPA 120 UL UPS

  • System power range 20kW–600kW
  • Nominal power/module 20kW
  • Nominal power/frame (capacity) 600kW
  • Output power factor 1.0
  • Topology Double conversion, transformerless, modular, Decentralized Parallel Architecture
  • Parallel configuration Up to 6 modules in one frame / up to 5 frames in parallel
  • Cable entry Bottom
  • Serviceability Front access only
  • Back-feed protection Built-in (standard)
  • Connection 5-wires, 3-phase + neutral + ground

INPUT

  • Nominal input voltage 3 x 208/120V + neutral + ground
  • Voltage tolerance < 100% (–15%, +10%), < 80% (–20%, +10%), < 60% (–30%, +10%)
  • Input distortion THDi < 4% at 100% load
  • Frequency range 50/60Hz ± 5%
  • Power factor 0.99 @ 100% load
  • Walk in/soft start Yes

OUTPUT

  • Rated output voltage 3 x 208/120V + neutral + ground
  • Voltage tolerance ± 2.5%
  • Voltage distortion THDv < 2% in linear mode
  • Frequency 50/60Hz

EFFICIENCY

  • AC-AC Up to 94% at nominal load

ENVIRONMENT

  • Protection rating IP 20
  • Storage temperature −25° to +70°C
  • Operating temperature 0° to +40°C
  • Altitude (above sea level) 1000 m without de-rating

BATTERIES

  • Number of 12V jars/string 25 – 35 jars
  • Types VRLA, NiCd
  • Battery charger Decentralized charger in each module set

COMMUNICATIONS

  • User interface Graphical touch screen (one per frame as standard) Decentralized LCD + mimic diagram (one per module as standard)
  • Communication ports USB, RS-232, voltage-free contacts, SNMP (optional)
  • Customer interface Remote shutdown, gen-set interface, external bypass contact

COMPLIANCY

  • Safety UL 1778 5th edition, CSA C22.2 No. 107.3-14 Third Edition
  • EMC IEC/EN 62040-2 C3
  • Manufacturing ISO 9001:2008

WEIGHT, DIMENSIONS

  • Weight (System with 6 modules) 1517 lbs. (688 kg)
  • Dimensions WxHxD 31.16″ x 77.76″ x 35.17″ (791 x 893 x 1975.5 mm)