Row Distribution Panel

With the ever increasing demands for power in a small footprint, the HD400 provides an unprecedented 230kW of power in about 14 cubic feet. Configured into a 9.5” deep enclosure, the HD400 can be positioned at the end of an of an server cabinet aisle, the wall of a cage or simply mount free-standing.

Each system provides two independent 400A/208V three phase (115kW) panelboards.

Options Include:
EPO Button
Surge Suppressor
Lightning Arrestor
Branch Circuit Monitoring
Transient Voltage Surge Suppression

The HD400 can support the following ‘redundant’ power configurations:

CabinetsLoad (per Cabinet)Input
215.0 kW30A/208V Single Phase [L6-30, L14-30]
148.6 kW30A/208V Three Phase [L15-30, L21-30]
1210 kW60A//208V Single Phase [IEC 309, 3W]
1014.4 kW50A/208V Three Phase [CS8365]
817 kW60A/208V Three Phase [IEC 309, 4W]

Row Distribution Panel

With the ever increasing demands for power in a small footprint, the HD400 provides an unprecedented 230kW of power in about 14 cubic feet. Configured into a 9.5” deep enclosure, the HD400 can be positioned at the end of an of an server cabinet aisle, the wall of a cage or simply mount free-standing.

Each system provides two independent 400A/208V three phase (115kW) panelboards.

Options Include:
EPO Button
Surge Suppressor
Lightning Arrestor
Branch Circuit Monitoring
Transient Voltage Surge Suppression

The HD400 can support the following ‘redundant’ power configurations:

CabinetsLoad (per Cabinet)Input
215.0 kW30A/208V Single Phase [L6-30, L14-30]
148.6 kW30A/208V Three Phase [L15-30, L21-30]
1210 kW60A//208V Single Phase [IEC 309, 3W]
1014.4 kW50A/208V Three Phase [CS8365]
817 kW60A/208V Three Phase [IEC 309, 4W]
Request a Quote
Features
  • Narrow design eliminates obstruction of aisle containment doors or curtains
  • Side-by-side A and B panel boards organize installations (Traditional RPPs are mounted on opposing sides)
  • Front access design reduces floor foot print & increases installation options (Traditional RPP requires full floor Tile & three side access)
  • Reduces excess panel board pole postions and unit cost (Traditional RPP requires four panel boards)
  • Advanced monitoring ties into BMS for mission critical applications (Traditional RPP typically provides only basic values)
  • Top or bottom access (Traditional RPP often requires top-hat to facilitate connections)
  • 1 Year Warranty (see terms)
  • UL Listed 478
Specifications
  • 400A Dual Feed (2N Configuration)
  • Input Circuit Breakers or Main Lug Only
  • Floor or Wall-mounted / Top or Bottom Feed
  • Dual 42 Pole Panels (84 Total) rated at 10kAIC
  • Optional integrated Branch Circuit Monitoring